64 Programming SATEL
– from zones [Zone al.msg.].
Fig. 8. Example of LCD keypad settings.
Code + card – in case of the INT-KLCDR and INT-KLFR keypads, you can define the
method of user authorization:
– code or card – the user can use code or card;
– code and card – the user must use both code and card;;
– the authorization method depends on the status of selected output (the output active –
code and card; the output inactive – code or card).
In case of the authorization using code and card, the executed function depends on
the second identifier.
The outputs 255 and 256 cannot be used for controlling the authorization method.